3.8.2. Output Stage Disable
The output amplifier is disabled during the power up sequence and recovery from a fault
condition. See sections 3.11 and 3.13 for details. The output amp can also be manually disabled
by grounding
the
TP4 "MUTE" test-point, or the Remote Shutdown input on
J4.6.
Grounding the
Remote Shutdown input will disable the output amp by initiating a continuous fault recovery
sequence, but grounding TP4 will not. Therefore, TP4 is useful for performing Notch Filter
Module tuning (see section 6.2).
For added motor protection a fuse Fl has been placed in-line with the output op-amp
U5.
See
the motor specifications for the proper fuse rating to be used with each servo configuration. To
momtor the voltage signal being sent to the scanner, clip a scope probe to one side ofthe fiise.
Use
TP2
or
W7.2
for
the
ground reference.
3.9. Reference Voltages
A voltage reference, U17 (LT1021-5), provides +5 volts for the overposition monitor. Command
Offset contiol, coil temperature calculator, and the DAC references. It is also converted to -5
volts through an inverting amplifier,
U16B.
The -5 volts is used in the ACJC circuit, overposition
monitor, and the DAC references. The +/-5 volts used for these various functions are labeled +/-
VREF,
so that they are not confused with the +5 volts used to power the digital circuitry. The
two reference voltages are available on W7.1 (+VREF) and W7.3 (-VREF) for extemal use
provided that no more than 2ma current is drawn from either of them. W7.2 is the ground
reference for these voltages.
3.10. Notch Filter Socket
The 670 Board is ready to accept a 6740-XX series Notch Filter Module (NFM). This module is
inserted into the J5 socket. If the NFM is not used, then pins
1
& 2 ofthe socket must be shorted
together. See appendix 6.2 for infoimation regarding the use ofthe 6740-XX NFM.
3.11.
Observation/Control Header
3.11.1
User Outputs
Various observation and contiol signals exist on
J4.
They are listed below:
J4.1 - Velocity out
Time derivative of position out signal (IK ohm output impedance).
Velocity Out = (5Vpos(t)/8t)^R100^C33
J4.2 - Position out
Position out signal (IK ohm output impedance). Position Out = Vpos(t)